Technical data

Table 1. Technical data MyVallox 245 CFi, aluminium
ObjectMyVallox 245 CFi
Product titles

MyVallox 245 CFi R

MyVallox 245 CFi L

Type code3734
Electrical connection230 V, 50 Hz, 14.5 A (power plug)
Enclosure protection classIP 34
Fans
  • Supply air — 0.17 kW 1.25 A EC
  • Extract air — 0.17 kW 1.25 A EC
Air volumes
  • Supply air — 226 dm3/s, 100 Pa
  • Extract air — 226 dm3/s, 100 Pa
Efficiencies
  • Annual efficiency — 83%
  • Supply air efficiency — 87%
  • Specific Fan Power SFP — 0.63 kW/m3/h (160 dm3/s)
Heat recovery bypassAutomatic
Post-heatingElectrical resistor, 1500 W
Pre-heating-
Additional heatingElectrical resistor, 1500 W
Filters
  • Supply air — ISO Coarse > 75% + ISO ePM1 ≥ 50 %
  • Extract air — ISO Coarse > 75%
Specific energy consumption (SEC)

In a cold climate — A+

Temperate climate — A+

Dimensions1038 x 1241 x 773 mm
Weight181 kg
Ventilation efficiency control
  • MyVallox control panel
  • MyVallox Home/Cloud user interface
  • CO2, %RH, and VOC control
  • Remote monitoring control (voltage signals, Modbus)
*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2020.
Table 2. Technical data MyVallox 245 CFi, enthalpy
ObjectMyVallox 245 CFi enthalpy
Product titles

MyVallox 245 CFi R enthalpy

MyVallox 245 CFi L enthalpy

Type code3735
Electrical connection230 V, 50 Hz, 14.5 A (power plug)
Enclosure protection classIP 34
Fans
  • Supply air — 0.170 kW 1.25 A EC
  • Extract air — 0.170 kW 1.25 A EC
Air volumes
  • Supply air — 229 dm3/s, 100 Pa
  • Extract air — 229 dm3/s, 100 Pa
Efficiencies
  • Supply air efficiency — 86%
  • Specific Fan Power SFP — 0.57 kW/m3/h (160 dm3/s)
Heat recovery bypassAutomatic
Post-heatingElectrical resistor, 1500 W
Pre-heating-
Additional heatingElectrical resistor, 1500 W
Filters
  • Supply air — ISO Coarse > 75% + ISO ePM1 ≥ 50 %
  • Extract air — ISO Coarse > 75%
Specific energy consumption (SEC)

In a cold climate — A+

Temperate climate — A+

Dimensions1038 x 1241 x 773 mm
Weight178.5 kg
Ventilation efficiency control
  • MyVallox control panel
  • MyVallox Home/Cloud user interface
  • CO2, %RH, and VOC control
  • Remote monitoring control (voltage signals, Modbus)
*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2020.
Table 3. Technical data MyVallox 245 CFi VKL
ObjectMyVallox 245 CFi VKL
Product titles

MyVallox 245 CFi VKL R

MyVallox 245 CFi VKL L

Type code3734
Electrical connection230 V, 50 Hz, 14.5 A (power plug)
Enclosure protection classIP 34
Fans
  • Supply air — 0.170 kW 1.25 A EC
  • Extract air — 0.170 kW 1.25 A EC
Air volumes
  • Supply air — 226 dm3/s, 100 Pa
  • Extract air — 227 dm3/s, 100 Pa
Efficiencies
  • Annual efficiency — 83%
  • Supply air efficiency — 87%
  • Specific Fan Power SFP — 0.68 kW/m3/h (158 dm3/s)
Heat recovery bypassAutomatic
Post-heatingLiquid radiator
Pre-heating-
Additional heatingElectrical resistor, 3000 W
Filters
  • Supply air — ISO Coarse > 75% + ISO ePM1 ≥ 50 %
  • Extract air — ISO Coarse > 75%
Specific energy consumption (SEC)

In a cold climate — A+

Temperate climate — A+

Dimensions1038 x 1241 x 773 mm
Weight187 kg
Ventilation efficiency control
  • MyVallox control panel
  • MyVallox Home/Cloud user interface
  • CO2, %RH, and VOC control
  • Remote monitoring control (voltage signals, Modbus)
*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2020.