Sound values

Table 1. Sound power level in the supply air duct
Sound power level in the supply air ducts by octave band L dB
Air flow l/s305075100125150175200225
Medium frequency of the octave band Hz63566065677074757879
125465160697474767776
250364652576772747677
500303949535861656868
1000233543495458626565
2000193040475256606363
4000171826354247515556
8000222222253238434748

L dB

576066727678808283

LWA´ dB(A)

354351576367707273
Table 2. Sound power level in the extract air duct
Sound power level in the extract air ducts by octave band L dB
Air flow l/s305075100125150175200225
Medium frequency of the octave band Hz63455153576164676970
125373951575456586060
250353643475363616566
500202531353943464849
1000111827333741444950
2000131420273236404344
4000171617182226313436
8000222222222222232526

L dB

465256606267697172

LWA´ dB(A)

303239444755545859
Table 3. Sound pressure level coming through the envelope
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)
Air flow l/s305075100125150175200225
LpA, dB (A)232328343942454948

The operating-point-specific sound values can be calculated with the Vallox MySelecta product selection program.