Sound values

Sound power level in the supply air duct by octave band L dB
Adjustment position (%)11284455627280100
Air flow dm3/s1023354349596572
Medium frequency of the octave band Hz635363717676797981
1254457667072757778
2503845535861656769
5002633414547515355
10002134404445485052
20001720263133373941
40001919202426303234
80002424242424252526

L dB

5364727777808283

LWA´ dB(A)

3344525758626365
Sound power level in the extract air duct by octave band L dB
Adjustment position (%)11284455627280100
Air flow dm3/s1122354448596471
Medium frequency of the octave band Hz635566737878828385
1254457667072767878
2503746556062676971
5003343444850545658
10002534414446495052
20001925343941454749
40001919242932363841
80002424242425272931
L dB5566747979838486
LWA´ dB(A)3546535859636566
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10 m2 sound absorption)
Adjustment position (%)11284455627280100
Air flow dm3/s (supply/extract)11/1422/2836/4143/5149/5859/6965/7572/83
LpA´ dB(A)2627313538404244

You can calculate the sound values for each operating point with the Vallox MySelecta control panel.