Sound values

Sound power level in the supply air duct (one duct) by octave band LW´ dB
Adjustment position (%)102030405060708090100
Medium frequency of the octave band Hz6357666669737577798082
12543525764666971727373
25041465055596474727375
50035414852555861646768
100030384348525558616465
200024334146505456596163
400017202734404549525557
800021212225313742464952

LW´ dB

58666670747780808284

LWA´ dB(A)

38455055596268687072
Sound power level in the extract air duct (one duct) by octave band LW´ dB
Adjustment position (%)102030405060708090100
Medium frequency of the octave band Hz6350515559646568727676
12538485053545557575959
25033394548526063636464
50024303639424649505253
100018263136394345485051
200013182530353841444647
400017171820242932353839
800021212121212223252830

LW´ dB

50535661656770737777

LWA´ dB(A)

30364044485356575959
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10 m2 sound absorption)
Adjustment position (%)102030405060708090100
LpA, dB (A)24262934394144474949

You can calculate the sound values for each operating point with the Vallox MySelecta control panel.