Technical specifications

Table 1. Technical specifications MyVallox 149 CFi, aluminium
ObjectMyVallox 149 CFi
Product titlesMyVallox 149 CFi XA
Type code3790
Electrical connection230 V, 50 Hz, 12.9 A power plug
Enclosure protection classIP34
Fans
  • Supply air — 0.17 kW 1.35 A EC
  • Extract air — 0.17 kW 1.35 A EC
Air volumes
  • Supply air — 145 dm3/s, 100 Pa
  • Extract air — 148 dm3/s, 100 Pa
Heat recovery bypassAutomatic
Post-heatingElectrical resistor, 900 W
Pre-heating-
Additional heatingElectrical resistor, 1500 W
Filters
  • Supply air — ISO Coarse > 75% + ISO ePM1 ≥ 60 %
  • Extract air — ISO Coarse > 75%
Specific energy consumption (SEC)

In a cold climate — A+

Temperate climate — A+

Efficiencies*
  • Annual efficiency — 83%
  • Supply air efficiency — 89%
  • Specific Fan Power (SFP) — 1.1 kW/m3/s (101 dm3/s)
Dimensions (w × h × d)643 x 932 x 540 mm
Weight78 kg
*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2020.
Table 2. Technical specifications MyVallox 149 CFi, enthalpy
ObjectMyVallox 149 CFi enthalpy
Product titlesMyVallox 149 CFi XE
Type code3791
Electrical connection230 V, 50 Hz, 12.9 A power plug
Enclosure protection classIP34
Fans
  • Supply air — 0.17 kW 1.35 A EC
  • Extract air — 0.17 kW 1.35 A EC
Air volumes
  • Supply air — 145 dm3/s, 100 Pa
  • Extract air — 148 dm3/s, 100 Pa
Heat recovery bypassAutomatic
Post-heatingElectrical resistor, 900 W
Pre-heating-
Additional heatingElectrical resistor, 1500 W
Filters
  • Supply air — ISO Coarse > 75% + ISO ePM1 ≥ 60 %
  • Extract air — ISO Coarse > 75%
Specific energy consumption (SEC)

In a cold climate — A+

Temperate climate — A+

Efficiencies*
  • Supply air efficiency — 89%
  • Specific Fan Power SFP — 1.1 kW/m3/s (101 dm3/s)
Dimensions (w × h × d)643 x 932 x 540 mm
Weight77 kg