Technical data

Table 1. Technical data MyVallox 99 CFi
ObjectMyVallox 99 CFi
Product titles

MyVallox 99 CFi R

MyVallox 99 CFi L

Type code3820
Electrical connection230 V, 50 Hz, 8.6 A power plug
Enclosure protection classIP34
Fans
  • Supply air — 0.1 kW 1.0 A EC
  • Extract air — 0.1 kW 1.0 A EC
Air volumes
  • Supply air — 97 dm3/s, 100 Pa
  • Extract air — 98 dm3/s, 100 Pa
Heat recovery bypassAutomatic
Post-heatingElectrical resistor, 900 W
Pre-heating-
Additional heatingElectrical resistor, 900 W
Filters
  • Supply air — ISO Coarse > 75% + ISO ePM1 ≥ 50 %
  • Extract air — ISO Coarse > 75%
Specific energy consumption (SEC)

In a cold climate — A+

In a temperate climate — A

Efficiencies*
  • Annual efficiency — 77%
  • Supply air efficiency — 82%
  • Specific Fan Power (SFP) — 1.15 kW/m3/s (68 dm3/s)
Dimensions (w × h × d)598 x 442 x 625 mm
Weight62 kg
*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2020.
Table 2. Technical data MyVallox 99 CFi enthalpy
ObjectMyVallox 99 CFi enthalpy
Product titles

MyVallox 99 CFi R enthalpy

MyVallox 99 CFi L enthalpy

Type code3821
Electrical connection230 V, 50 Hz, 8.6 A power plug
Enclosure protection classIP34
Fans
  • Supply air — 0.1 kW 1.0 A EC
  • Extract air — 0.1 kW 1.0 A EC
Air volumes
  • Supply air — 95 dm3/s, 100 Pa
  • Extract air — 99 dm3/s, 100 Pa
Heat recovery bypassAutomatic
Post-heatingElectrical resistor, 900 W
Pre-heating-
Additional heatingElectrical resistor, 900 W
Filters
  • Supply air — ISO Coarse > 75% + ISO ePM1 ≥ 50 %
  • Extract air — ISO Coarse > 75%
Specific energy consumption (SEC)

In a cold climate — A+

In a temperate climate — A

Efficiencies*
  • Supply air efficiency — 84%
  • Specific Fan Power (SFP) — 1.3 kW/m3/s (67 dm3/s)
Dimensions (w × h × d)598 x 442 x 625 mm
Weight62 kg
*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2020.