Sound values

Table 1. Sound power level in the supply air duct
Sound power level in the supply air ducts by octave band L dB
Air flow l/s102030405060708095
Medium frequency of the octave band Hz63626367697381808382
125535458616366686970
250525461646668707272
500454955606367727272
1000374249555862656869
2000253141485357606364
4000182132404550545758
8000222223283541465051

L dB

636469717582818484

LWA´ dB(A)

475057616468727374
Table 2. Sound power level in the extract air duct
Sound power level in the extract air ducts by octave band L dB
Air flow l/s102030405060708095
Medium frequency of the octave band Hz63555656636974788283
125414647515457616668
250323543485051545658
500232632374246495152
1000162127323740434648
2000131317232832353941
4000161617171922262932
8000212221222222222325

L dB

555757646974788283

LWA´ dB(A)

323538434751555859
Table 3. Sound pressure level coming through the envelope
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)
Air flow l/s10203040506070809095
LpA, dB (A)22262730343739424342

The operating-point-specific sound values can be calculated with the Vallox MySelecta product selection program.