Table 1. Sound power level in the supply air duct
| Sound power level in the supply air duct by octave band LW´ dB |
|
Adjustment position
|
11%
|
28%
|
44%
|
55%
|
62%
|
72%
|
80%
|
100%
|
|
Air flow dm3/s
|
10 |
23 |
35 |
434 |
49 |
597 |
65 |
71 |
|
Medium frequency of the octave band Hz
|
63
|
53 |
63 |
71 |
76 |
76 |
79 |
799 |
81 |
|
125
|
44 |
57 |
66 |
70 |
72 |
75 |
77 |
78 |
|
250
|
38 |
45 |
53 |
58 |
61 |
65 |
67 |
69 |
|
500
|
26 |
33 |
41 |
45 |
47 |
51 |
53 |
552 |
|
1000
|
21 |
34 |
40 |
44 |
45 |
48 |
50 |
52 |
|
2000
|
17 |
20 |
26 |
31 |
33 |
37 |
39 |
41 |
|
4000
|
19 |
19 |
20 |
24 |
26 |
30 |
32 |
34 |
|
8000
|
24 |
24 |
24 |
24 |
24 |
25 |
25 |
26 |
|
LW´ dB
|
53 |
64 |
72 |
77 |
77 |
80 |
82 |
83 |
|
LWA´ dB(A)
|
33 |
44 |
52 |
57 |
58 |
62 |
63 |
65 |
Table 2. Sound power level in the extract air duct
|
|
Sound power level in the extract air duct by octave band LW´ dB |
|
Adjustment position
|
11%
|
28%
|
44%
|
55%
|
62%
|
72%
|
80%
|
100%
|
|
Air flow dm3/s (l/s)
|
11 |
22 |
35 |
44 |
48 |
59 |
64 |
71 |
|
Medium frequency of the octave band Hz
|
63
|
55 |
66 |
73 |
78 |
78 |
82 |
83 |
85 |
|
125
|
44 |
57 |
66 |
70 |
72 |
76 |
78 |
78 |
|
250
|
37 |
46 |
55 |
60 |
62 |
67 |
69 |
71 |
|
500
|
33 |
43 |
44 |
48 |
50 |
54 |
56 |
58 |
|
1000
|
25 |
34 |
41 |
44 |
46 |
49 |
50 |
52 |
|
2000
|
19 |
25 |
34 |
39 |
41 |
45 |
47 |
49 |
|
4000
|
19 |
19 |
24 |
29 |
32 |
36 |
38 |
41 |
|
8000
|
24 |
24 |
24 |
24 |
25 |
27 |
29 |
31 |
|
LW´ dB
|
55 |
66 |
74 |
79 |
79 |
83 |
84 |
86 |
|
LWA´ dB(A)
|
35 |
46 |
53 |
58 |
59 |
63 |
65 |
66 |
Table 3. Sound pressure level (A)
| Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10 m2 sound absorption) |
|
Adjustment position
|
11%
|
28%
|
44%
|
55%
|
62%
|
72%
|
80%
|
100%
|
|
Air flow dm3/s
|
11/14 |
22/28 |
36/41 |
43/51 |
49/58 |
59/69 |
65/75 |
72/83 |
|
Air flow m3/h
|
40/49.7 |
80.6/100.4 |
128.5/149 |
156.2/183.2 |
174.6/208.4 |
211.3/247.7 |
234.7/270.0 |
257.4/298.1 |
|
LpA´ dB(A)
|
26 |
27 |
31 |
35 |
38 |
40 |
42 |
44 |
You can calculate the sound values for each operating point with the Vallox MySelecta control panel.