Technical data

ObjectVallox 145 MV
Product titles

Vallox 145 MV R

Vallox 145 MV L

Type codeA3712
Electrical connection230 V, 50 Hz, 11.9 A power plug
Enclosure protection classIP34
Fans
  • Supply air — 0.175 kW 1.25 A EC
  • Extract air — 0.175 kW 1.25 A EC
Air volumes
  • Supply air — 142 dm3/s, 100 Pa
  • Extract air — 160 dm3/s, 100 Pa
Efficiencies*
  • Annual efficiency — 79%
  • Supply air efficiency — 85%
  • Specific Fan Power SFP — 1.25 kW/m3/h (100 dm3/s)
Heat recovery bypassAutomatic
Post-heatingElectrical resistor, 900 W
Pre-heating-
Additional heatingElectrical resistor, 1500 W
Filters
  • Supply air — ISO Coarse > 75% + ISO ePM1 ≥ 50%
  • Extract air — ISO Coarse > 75%
Specific energy consumption (SEC)

In a cold climate — A+

In a temperate climate — A

Dimensions717 x 748 x 578 mm
Weight80 kg
*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2020.