Table 1. Sound power level in the supply air duct
| Sound power level in the supply air duct (one duct) by octave band LW´ dB |
|
Adjustment position (%)
|
10
|
20
|
30
|
40
|
50
|
60
|
70
|
80
|
90
|
100
|
|
Medium frequency of the octave band Hz
|
63
|
55 |
66 |
73 |
76 |
80 |
83 |
85 |
86 |
87 |
87 |
|
125
|
50 |
58 |
64 |
68 |
72 |
76 |
80 |
83 |
84 |
84 |
|
250
|
52 |
57 |
63 |
65 |
68 |
72 |
74 |
77 |
78 |
78 |
|
500
|
41 |
48 |
53 |
57 |
61 |
64 |
67 |
70 |
71 |
71 |
|
1000
|
53 |
47 |
52 |
57 |
60 |
64 |
65 |
67 |
68 |
68 |
|
2000
|
23 |
34 |
43 |
48 |
53 |
58 |
62 |
64 |
66 |
66 |
|
4000
|
18 |
23 |
36 |
44 |
50 |
55 |
59 |
62 |
63 |
63 |
|
8000
|
21 |
22 |
28 |
39 |
47 |
54 |
58 |
62 |
63 |
63 |
|
LW, dB
|
59 |
68 |
74 |
77 |
81 |
84 |
86 |
88 |
90 |
89 |
|
LWA, dB(A)
|
53 |
52 |
58 |
62 |
66 |
69 |
72 |
75 |
76 |
76 |
Table 2. Sound power level in the extract air duct
| Sound power level in the extract air duct (one duct) by octave band LW´ dB |
|
Adjustment position (%)
|
10
|
20
|
30
|
40
|
50
|
60
|
70
|
80
|
90
|
100
|
|
Medium frequency of the octave band Hz
|
63
|
53 |
58 |
63 |
67 |
73 |
78 |
78 |
79 |
80 |
79 |
|
125
|
45 |
50 |
56 |
61 |
65 |
69 |
73 |
75 |
75 |
75 |
|
250
|
40 |
39 |
44 |
49 |
54 |
57 |
60 |
63 |
64 |
64 |
|
500
|
30 |
37 |
43 |
47 |
50 |
53 |
56 |
58 |
59 |
59 |
|
1000
|
32 |
33 |
36 |
41 |
44 |
48 |
50 |
52 |
53 |
53 |
|
2000
|
15 |
22 |
30 |
34 |
38 |
42 |
45 |
48 |
49 |
49 |
|
4000
|
17 |
17 |
19 |
23 |
27 |
31 |
35 |
38 |
39 |
39 |
|
8000
|
21 |
21 |
21 |
22 |
24 |
28 |
32 |
35 |
36 |
36 |
|
LW, dB
|
54 |
59 |
64 |
68 |
74 |
79 |
79 |
80 |
81 |
81 |
|
LWA, dB(A)
|
37 |
40 |
45 |
50 |
54 |
58 |
60 |
63 |
63 |
63 |
Table 3. Sound pressure level (A)
| Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10 m2 sound absorption) |
|
Adjustment position
|
10%
|
20%
|
30%
|
40%
|
50%
|
60%
|
70%
|
80%
|
90%
|
100%
|
|
LpA´ dB(A)
|
28 |
27 |
32 |
35 |
39 |
43 |
46 |
48 |
49 |
49 |
You can calculate the sound values for each operating point with the Vallox MySelecta control panel.