Sound values

Sound power level in the supply air duct (one duct) by octave band L dB
Adjustment position (%)1020304050607080100
Medium frequency of the octave band Hz63616568737379808184
125576164656871727481
250576471656769717374
500434858636062647076
1000434954586164676770
2000334147515457596264
4000233240454953555759
8000212432384347505355
LW, dB646973757681818287
LWA, dB(A)515764646568707276
Sound power level in the extract air duct (one duct) by octave band L dB
Adjustment position (%)1020304050607080100
Medium frequency of the octave band Hz63566166697478798182
125485358626467697278
250465055586164666768
500303643464956525456
1000243035394245474850
2000162127323539414344
4000161720242831343637
8000202020212325283032
LW, dB576267707578808284
LWA, dB(A)404449535659606265
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10 m2 sound absorption)
Adjustment position (%)1020304050607080100
LpA, dB (A)263036414344454747

You can calculate the sound values for each operating point with the Vallox MySelecta control panel.