Sound values

Sound power level in the supply air duct (one duct) by octave band LW´ dB
Adjustment position (%)1020304050607080100
Medium frequency of the octave band Hz63536067717478818384
125485661667074767880
250465358626569717476
500404856576062656769
1000314250555861646567
2000183240465256606264
4000172030384449535658
8000212125344248535759
LW, dB556269737680838586
LWA, dB(A)414956606367697273
Sound power level in the extract air duct (one duct) by octave band LW´ dB
Adjustment position (%)1020304050607080100
Medium frequency of the octave band Hz63545662656972757779
125424450535861646668
250344146505356606264
500263540434649525556
1000182734384144475051
2000131724293336394244
4000171717182023273133
8000212121212122242629
LW, dB555762667072757879
LWA, dB(A)323843465053565960
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10 m2 sound absorption)
Adjustment position (%)1020304050607080100
LpA´ dB(A)212430323539424547

You can calculate the sound values for each operating point with the Vallox MySelecta control panel.