Supply/extract air volumes and input powers

Abbreviations used in the table have been explained below:

  • A — Pressure loss in ducts. Total pressure (Pa)

  • B — Volume flow rate (dm3/s)

  • Continuous line (—) — Extract air

  • Broken line (┄) — Supply air

  • PK — An example of pressure loss in the extract air ducts.

  • TK — An example of pressure loss in the supply air ducts.

  • SFP = Input power (total) (W) Airflow specified in the ventilation plan (max)(l/s)

    SFP rate (Specific Fan Power) recommended value <1.8 (kW m3/s). When a lower total pressure is used, also the SFP of the speed is lowered.

Figure 15. Supply and extract air volumes

Supply and extract air volumes

Table 20. Fan input power

Fan speedsExtract air flow (50Pa) dm3/sCombined input power of the fans W
21%-12
35%1018
41%2225
50%3334
56%4650
65%6075
72%75117
100%92185

Figure 16. Fan input power

Fan input power