Table 1. Sound power level in the supply air duct| Sound power level in the supply air duct (one duct) by octave band LW’, dB |
|---|
| Adjustment position (%)
| 10
| 20
| 30
| 40
| 50
| 60
| 70
| 80
| 90
| 100
|
| Medium frequency of the octave band Hz
| 63
| 62 | 62 | 65 | 66 | 70 | 71 | 73 | 74 | 77 | 79 |
| 125
| 52 | 55 | 57 | 59 | 62 | 63 | 65 | 66 | 68 | 68 |
| 250
| 52 | 58 | 61 | 64 | 68 | 66 | 67 | 68 | 69 | 70 |
| 500
| 47 | 52 | 56 | 60 | 63 | 79 | 72 | 81 | 76 | 75 |
| 1000
| 39 | 45 | 50 | 54 | 58 | 61 | 63 | 64 | 66 | 67 |
| 2000
| 27 | 36 | 43 | 48 | 52 | 55 | 57 | 59 | 62 | 62 |
| 4000
| 19 | 26 | 35 | 41 | 45 | 50 | 52 | 54 | 56 | 57 |
| 8000
| 21 | 21 | 23 | 28 | 33 | 39 | 43 | 46 | 48 | 49 |
| LW, dB
| 63 | 64 | 67 | 70 | 73 | 80 | 77 | 82 | 80 | 81 |
| LWA, dB(A)
| 48 | 53 | 57 | 61 | 64 | 76 | 71 | 78 | 75 | 74 |
Table 2. Sound power level in the extract air duct| Sound power level in the extract air duct (one duct) by octave band LW´ dB |
|---|
| Adjustment position (%)
| 10
| 20
| 30
| 40
| 50
| 60
| 70
| 80
| 90
| 100
|
| Medium frequency of the octave band Hz
| 63
| 53 | 52 | 56 | 62 | 65 | 69 | 71 | 71 | 73 | 74 |
| 125
| 43 | 46 | 49 | 52 | 55 | 59 | 62 | 65 | 66 | 67 |
| 250
| 35 | 41 | 54 | 47 | 50 | 52 | 54 | 56 | 57 | 58 |
| 500
| 24 | 30 | 35 | 39 | 43 | 48 | 50 | 52 | 57 | 53 |
| 1000
| 20 | 26 | 31 | 35 | 38 | 41 | 44 | 46 | 48 | 49 |
| 2000
| 13 | 15 | 20 | 24 | 27 | 31 | 33 | 36 | 38 | 38 |
| 4000
| 17 | 17 | 17 | 18 | 20 | 23 | 26 | 28 | 30 | 31 |
| 8000
| 21 | 21 | 21 | 21 | 21 | 21 | 22 | 22 | 23 | 24 |
| LW, dB
| 53 | 53 | 59 | 62 | 66 | 69 | 72 | 72 | 74 | 76 |
| LWA, dB(A)
| 33 | 36 | 46 | 43 | 47 | 50 | 52 | 55 | 57 | 57 |
Table 3. Sound pressure level coming through the envelope| Sound pressure level coming through the envelope of the unit in the room in which it is installed (10 m2 sound absorption) |
|---|
| Adjustment position (%)
| 10
| 20
| 30
| 40
| 50
| 60
| 70
| 80
| 90
| 100
|
| LpA´ dB(A)
| 22 | 25 | 28 | 32 | 34 | 36 | 38 | 43 | 41 | 41 |
You can calculate the sound values for each operating point with the Vallox MySelecta control panel.