Technical specifications

ObjectMyVallox 125 CFi
Product titles

MyVallox 125 CFi R

MyVallox 125 CFi L

Type code3766
Electrical connection230 V, 50 Hz, 9.3 A power plug
Enclosure protection classIP34
Fans
  • Supply air — 0.17 kW 1.35 A EC
  • Extract air — 0.17 kW 1.35 A EC
Air volumes
  • Supply air — 107 dm3/s, 100 Pa
  • Extract air — 111 dm3/s, 100 Pa
Heat recovery bypassAutomatic
Post-heatingElectrical resistor, 900 W
Pre-heating-
Additional heatingElectrical resistor, 900 W
Filters
  • Supply air — ISO Coarse > 75% + ISO ePM1 ≥ 50 %
  • Extract air — ISO Coarse > 75%
Specific energy consumption (SEC)

In a cold climate — A+

In a temperate climate — A

Efficiencies*
  • Annual efficiency — 75%
  • Supply air efficiency — 81%
  • Specific Fan Power (SFP) — 1.54 kW/m3/s (75 dm3/s)
Dimensions (w × h × d)598 x 525 x 601 mm
Weight66 kg
*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2020.