Table 1. Sound power level in the supply air duct| Sound power level in the supply air duct (one duct) by octave band LW´ dB |
|---|
|
Adjustment position (%)
|
10
|
20
|
30
|
40
|
50
|
60
|
70
|
80
|
90
|
100
|
|
Medium frequency of the octave band Hz
|
63
| 57 | 61 | 65 | 68 | 70 | 74 | 75 | 78 | 79 | 79 |
|
125
| 44 | 47 | 52 | 56 | 60 | 63 | 66 | 68 | 70 | 70 |
|
250
| 34 | 41 | 46 | 50 | 53 | 57 | 59 | 62 | 64 | 64 |
|
500
| 26 | 35 | 41 | 44 | 48 | 51 | 53 | 55 | 58 | 58 |
|
1000
| 17 | 24 | 30 | 34 | 38 | 41 | 44 | 47 | 49 | 49 |
|
2000
| 13 | 15 | 20 | 24 | 28 | 32 | 35 | 37 | 40 | 40 |
|
4000
| 17 | 17 | 17 | 18 | 21 | 23 | 26 | 28 | 31 | 31 |
|
8000
| 21 | 21 | 21 | 21 | 21 | 21 | 22 | 23 | 25 | 25 |
|
LW, dB
| 57 | 61 | 65 | 68 | 71 | 74 | 76 | 78 | 79 | 79 |
|
LWA, dB(A)
| 34 | 39 | 44 | 47 | 51 | 54 | 56 | 59 | 60 | 60 |
Table 2. Sound power level in the extract air duct| Sound power level in the extract air duct (one duct) by octave band LW´ dB |
|---|
|
Adjustment position (%)
|
10
|
20
|
30
|
40
|
50
|
60
|
70
|
80
|
90
|
100
|
|
Medium frequency of the octave band Hz
|
63
| 51 | 56 | 63 | 66 | 70 | 73 | 76 | 78 | 79 | 79 |
|
125
| 43 | 46 | 52 | 55 | 60 | 63 | 66 | 68 | 71 | 71 |
|
250
| 33 | 38 | 44 | 47 | 51 | 55 | 58 | 61 | 63 | 63 |
|
500
| 29 | 38 | 44 | 47 | 51 | 54 | 57 | 59 | 61 | 61 |
|
1000
| 24 | 32 | 38 | 42 | 46 | 49 | 52 | 55 | 57 | 57 |
|
2000
| 13 | 17 | 24 | 29 | 33 | 36 | 39 | 42 | 44 | 44 |
|
4000
| 17 | 17 | 18 | 20 | 23 | 26 | 29 | 32 | 34 | 34 |
|
8000
| 21 | 21 | 21 | 21 | 21 | 22 | 23 | 25 | 27 | 27 |
|
LW, dB
| 52 | 56 | 64 | 66 | 71 | 74 | 76 | 79 | 80 | 80 |
|
LWA, dB(A)
| 33 | 39 | 45 | 48 | 52 | 55 | 58 | 61 | 63 | 63 |
Table 3. Sound pressure level (A)| Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10 m2 sound absorption) |
|---|
|
Adjustment position
|
10%
|
20%
|
30%
|
40%
|
50%
|
60%
|
70%
|
80%
|
90%
|
100%
|
|
LpA´ dB(A)
| 24 | 28 | 34 | 33 | 37 | 41 | 44 | 46 | 48 | 48 |
You can calculate the sound values for each operating point with the Vallox MySelecta control panel.