Heating season setting
Use the
Plus and Minus buttons to select the heating season
setting.The adjustment
range is 0 °C to +19 °C. The factory setting is +12
°C.
Seasonal heating is
triggered by the outside air temperature.
- When the outside air temperature falls below the set value, post-heating is used, if necessary, to heat the supply air. Bypass is always 100% in heat recovery.
- When outside air temperature is abowe the reference value, seasonal heating is disabled. Suply air heater is not in use. Bypass and partial bypass is in use.