Vallox 90K MV

Table 1. Technical data
Object Vallox 90K MV
Product titles

Vallox 90K MV R

Vallox 90K MV L

Type code A3528
Product numbers

3008-001 (R model)

3009-001 (L model)

Electrical connection 230 V, 50 Hz ≈ 5,7 A (power plug)
Enclosure protection class IP 34
Fans
  • Extract air — 0.119 kW 0.9 A
  • Supply air — 0.119 kW 0.9 A
Air volumes
  • Supply air — 73 dm3/s (259 m3/h) 100 Pa
  • Extract air — 84 dm3/s (302 m3/h) 100 Pa
Efficiencies
  • Annual efficiency — 74%
  • Supply air efficiency — 83%
  • Specific Fan Power (SFP) — 1.1 (50 dm3/s) B
Heat recovery Cross-counter flow cell, η = approx. 80%
Heat recovery bypass Automatic
Post-heating Electrical resistor, 900 W
Pre-heating -
Additional heating -
Filters
  • Supply air — ISO Coarse > 75% + ISO ePM1
  • Extract air — ISO Coarse > 75%
Specific energy consumption (SEC)
  • In a cold climate — A+
  • In a temperate climate — A
Dimensions without the siphon (width x height x depth) 597x798x346mm
Weight 52 kg
Ventilation efficiency control
  • MyVallox Control panel
  • MyVallox Home/Cloud user interface
  • CO2, %RH, and VOC control
  • Remote monitoring control (voltage message, Modbus)
Accessories
  • MyVallox carbon dioxide sensor (optional)
  • MyVallox humidity sensor (optional)
  • MyVallox VOC sensor
  • MyVallox KNX bus adapter
Annual efficiency classification of heat recovery from extract air B