Table 1. Vallox 110 MV — Sound power level in the supply air duct
Sound power level in the supply air duct (one duct) by octave band LW´ dB |
Adjustment position (%)
|
10
|
20
|
30
|
40
|
50
|
60
|
70
|
80
|
90
|
100
|
Medium frequency of the octave band Hz
|
63
|
53 |
60 |
67 |
71 |
74 |
78 |
82 |
83 |
84 |
84 |
125
|
48 |
56 |
61 |
66 |
70 |
74 |
76 |
78 |
80 |
80 |
250
|
46 |
53 |
58 |
62 |
65 |
69 |
71 |
74 |
76 |
76 |
500
|
40 |
48 |
56 |
57 |
60 |
62 |
65 |
67 |
68 |
69 |
1000
|
31 |
42 |
50 |
55 |
58 |
61 |
64 |
65 |
67 |
67 |
2000
|
18 |
32 |
40 |
46 |
52 |
56 |
60 |
62 |
64 |
64 |
4000
|
17 |
20 |
30 |
38 |
44 |
49 |
53 |
56 |
59 |
59 |
8000
|
21 |
21 |
25 |
34 |
42 |
48 |
53 |
57 |
59 |
60 |
LW, dB
|
55 |
62 |
69 |
73 |
76 |
80 |
83 |
85 |
86 |
86 |
LWA, dB(A)
|
41 |
49 |
56 |
60 |
63 |
67 |
69 |
72 |
73 |
73 |
Table 2. Vallox 110 MV — Sound power level in the extract air duct
Sound power level in the extract air duct (one duct) by octave band LW´ dB |
Adjustment position (%)
|
10
|
20
|
30
|
40
|
50
|
60
|
70
|
80
|
90
|
100
|
Medium frequency of the octave band Hz
|
63
|
54 |
46 |
62 |
65 |
69 |
72 |
75 |
77 |
79 |
79 |
125
|
42 |
44 |
50 |
53 |
58 |
61 |
64 |
66 |
68 |
68 |
250
|
34 |
41 |
46 |
50 |
53 |
56 |
60 |
62 |
64 |
64 |
500
|
26 |
35 |
40 |
43 |
46 |
49 |
52 |
55 |
57 |
57 |
1000
|
18 |
28 |
34 |
38 |
41 |
45 |
47 |
50 |
52 |
51 |
2000
|
13 |
17 |
24 |
29 |
33 |
36 |
39 |
42 |
44 |
44 |
4000
|
17 |
17 |
18 |
19 |
21 |
24 |
27 |
31 |
33 |
33 |
8000
|
21 |
21 |
21 |
21 |
21 |
22 |
24 |
26 |
29 |
29 |
LW, dB
|
55 |
57 |
62 |
66 |
70 |
72 |
75 |
78 |
79 |
79 |
LWA, dB(A)
|
33 |
38 |
43 |
46 |
50 |
53 |
56 |
59 |
60 |
60 |
Table 3. Vallox 110 MV — Sound pressure level (A)
Sound power level in the extract air
duct (one duct) by octave band |
Adjustment position
|
10
|
20%
|
30%
|
40%
|
50%
|
60%
|
70%
|
80%
|
90
|
100%
|
LpA´ dB(A)
|
21 |
24 |
30 |
32 |
35 |
39 |
42 |
45 |
47 |
47 |
You can calculate the sound values for each operating point with the Vallox
MySelecta software.