Sound values
Sound power level in the supply air duct (one duct) by octave band Lw, dB Adjustment position |
|||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Adjustment position (%) | 10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 100 | ||
Air flow dm3/s | 15 | 24 | 34 | 42 | 51 | 62 | 69 | 77 | 83 | ||
Air flow m3/h | 54 | 86 | 122 | 151 | 184 | 223 | 248 | 277 | 299 | ||
Medium frequency of the octave band Hz | 63 | 62 | 64 | 69 | 73 | 77 | 82 | 84 | 87 | 88 | |
125 | 53 | 63 | 65 | 65 | 67 | 71 | 74 | 76 | 78 | ||
250 | 48 | 56 | 60 | 65 | 70 | 71 | 73 | 75 | 75 | ||
500 | 43 | 49 | 56 | 60 | 64 | 67 | 69 | 71 | 73 | ||
1000 | 35 | 43 | 49 | 53 | 56 | 61 | 64 | 65 | 67 | ||
2000 | 25 | 36 | 44 | 49 | 52 | 56 | 58 | 61 | 62 | ||
4000 | 18 | 23 | 32 | 38 | 43 | 48 | 51 | 54 | 55 | ||
8000 | 21 | 22 | 29 | 37 | 43 | 49 | 52 | 55 | 57 | ||
LW, dB | 63 | 67 | 71 | 74 | 78 | 83 | 85 | 88 | 88 | ||
LWA, dB (A) | 43 | 53 | 57 | 61 | 65 | 68 | 71 | 72 | 74 |
Sound power level in the extract air duct (one duct) by octave band Lw, dB Adjustment position |
|||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Adjustment position (%) | 10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 100 | ||
Air flow dm3/s | 23 | 31 | 41 | 50 | 60 | 70 | 78 | 86 | 92 | ||
Air flow m3/h | 83 | 112 | 148 | 180 | 216 | 252 | 281 | 310 | 331 | ||
Medium frequency of the octave band Hz | 63 | 54 | 55 | 62 | 66 | 69 | 75 | 78 | 79 | 80 | |
125 | 46 | 50 | 53 | 56 | 59 | 62 | 65 | 67 | 68 | ||
250 | 39 | 45 | 51 | 55 | 60 | 59 | 61 | 62 | 64 | ||
500 | 29 | 35 | 40 | 44 | 47 | 50 | 55 | 54 | 56 | ||
1000 | 16 | 24 | 30 | 34 | 37 | 40 | 43 | 46 | 46 | ||
2000 | 13 | 17 | 23 | 28 | 32 | 36 | 38 | 41 | 42 | ||
4000 | 17 | 17 | 18 | 20 | 24 | 28 | 30 | 33 | 35 | ||
8000 | 21 | 21 | 21 | 21 | 22 | 23 | 25 | 28 | 29 | ||
LW, dB | 54 | 57 | 63 | 66 | 70 | 75 | 78 | 79 | 80 | ||
LWA, dB (A) | 35 | 40 | 45 | 49 | 53 | 55 | 58 | 59 | 60 |
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10 m2 sound absorption) Adjustment position / Air flows (supply/extract) | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Adjustment position (%) | 10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 100 | |
Air flow dm3/s | 15/20 | 24/30 | 33/40 | 42/48 | 52/58 | 61/68 | 70/76 | 78/84 | 83/89 | |
Air flow m3/h | 54/72 | 86/108 | 119/144 | 151/173 | 187/209 | 220/245 | 252/274 | 281/302 | 299/320 | |
LpA, dB (A) | 22 | 27 | 32 | 35 | 38 | 43 | 44 | 46 | 47 |