Sound values
Sound power level in the supply air duct (one duct) by octave band LW´ dB | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Adjustment position (%) | 10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 | |
Medium frequency of the octave band Hz | 63 | 57 | 61 | 65 | 68 | 70 | 74 | 75 | 78 | 79 | 79 |
125 | 44 | 47 | 52 | 56 | 60 | 63 | 66 | 68 | 70 | 70 | |
250 | 34 | 41 | 46 | 50 | 53 | 57 | 59 | 62 | 64 | 64 | |
500 | 26 | 35 | 41 | 44 | 48 | 51 | 53 | 55 | 58 | 58 | |
1000 | 17 | 24 | 30 | 34 | 38 | 41 | 44 | 47 | 49 | 49 | |
2000 | 13 | 15 | 20 | 24 | 28 | 32 | 35 | 37 | 40 | 40 | |
4000 | 17 | 17 | 17 | 18 | 21 | 23 | 26 | 28 | 31 | 31 | |
8000 | 21 | 21 | 21 | 21 | 21 | 21 | 22 | 23 | 25 | 25 | |
LW, dB | 57 | 61 | 65 | 68 | 71 | 74 | 76 | 78 | 79 | 79 | |
LWA, dB(A) | 34 | 39 | 44 | 47 | 51 | 54 | 56 | 59 | 60 | 60 |
Sound power level in the extract air duct (one duct) by octave band LW´ dB | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Adjustment position (%) | 10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 | |
Medium frequency of the octave band Hz | 63 | 51 | 56 | 63 | 66 | 70 | 73 | 76 | 78 | 79 | 79 |
125 | 43 | 46 | 52 | 55 | 60 | 63 | 66 | 68 | 71 | 71 | |
250 | 33 | 38 | 44 | 47 | 51 | 55 | 58 | 61 | 63 | 63 | |
500 | 29 | 38 | 44 | 47 | 51 | 54 | 57 | 59 | 61 | 61 | |
1000 | 24 | 32 | 38 | 42 | 46 | 49 | 52 | 55 | 57 | 57 | |
2000 | 13 | 17 | 24 | 29 | 33 | 36 | 39 | 42 | 44 | 44 | |
4000 | 17 | 17 | 18 | 20 | 23 | 26 | 29 | 32 | 34 | 34 | |
8000 | 21 | 21 | 21 | 21 | 21 | 22 | 23 | 25 | 27 | 27 | |
LW, dB | 52 | 56 | 64 | 66 | 71 | 74 | 76 | 79 | 80 | 80 | |
LWA, dB(A) | 33 | 39 | 45 | 48 | 52 | 55 | 58 | 61 | 63 | 63 |
Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10 m2 sound absorption) | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Adjustment position | 10% | 20% | 30% | 40% | 50% | 60% | 70% | 80% | 90% | 100% |
LpA´ dB(A) | 24 | 28 | 34 | 33 | 37 | 41 | 44 | 46 | 48 | 48 |