Removing and cleaning the extract air fan (B)
To clean the extract air fan:
- Disconnect the ventilation unit from the mains electricity supply.
- Lift the latch to open the door of the ventilation unit.
-
Lift the door off.
CAUTION: The door is heavy.
- The fan has been fastened on the mounting plate with wing bolts (2). Remove the wing bolts and lift the fan out of the unit.
- Disconnect the quick connector of the fan cable (3).
- Clean the fan. The fan blades can be cleaned with compressed air (wear protective goggles) or by brushing them gently. Do not remove or move the fan blade balancing weights.
- To reassemble the ventilation unit, follow the above steps in reverse order.
- Close the door of the unit. Ensure that the safety switch catch of the door is touching the safety switch, allowing the unit to be turned on.
- Plug the ventilation unit back into the mains.
- The extract air fan has now been checked and cleaned.