Digital input 1 and 2

To edit the digital input 1 or 2 of the ventilation unit:

  1. Select Expert settings.
  2. Select Digital input 1 or 2 in the Input settings area.
  3. Select the function of the digital input from the list.

    The options are:

    • None — The input is not enabled.
    • Custom mode off / on, 0V / 24V — If 24 V is fed into the digital input, the unit will use the Custom mode. If 0 V is fed into the digital input, the unit will use the last ventilation mode that was used.
    • At home / Away, 0V / 24V — If 0 V is fed into the digital input, the unit will use the At home mode. If 24 V is fed into the digital input, the unit will use the Away mode.
    • Forced custom mode off / on, 0V / 24V — If 24 V is fed into the digital input, the unit will use the Custom mode. If 0 V is fed into the digital input, the unit will use the last ventilation mode that was used.
    • Emergency stop / Normal operation, 0V / 24V — If 0V is fed into the digital input, the emergency stop is activated. If 24 V is fed into the digital input, the unit will use the last ventilation mode that was used.
    • Boost off / on, 0V / 24V — If 24 V is fed into the digital input, the unit will use the Boost mode for the period specified in the timer. If 0 V is fed into the digital input, the unit will use the last ventilation mode that was used.
    • Normal operation / HR cell bypass, 0V / 24V — If 0 V is fed into the digital input, the automatic mode is activated. If 24 V is fed into the digital input, the bypass mode is activated.
    • Week clock off / on, 0V / 24V — If 24V is fed into the digital input, the Week clock is turned on. If 0 V is fed into the digital input, the week clock is turned off.
    • Programmable input off/on,0V / 24V — If 24 V is fed to the programmable input, the programmable input is enabled. If 0 V is fed to the programmable input, the programmable input is disabled. See Programmable input.