Removal of condensing water

The Vallox Silent Klick siphon package is delivered with the unit. The package allows for leading the water condensed from the extract air to the floor drain. The standard siphon that is equipped with an air lock requires 75 mm of free space underneath the ventilation unit when installed. The air lock ensures the removal of condensing water and muffles any noise related to the drying of the siphon. In low-ceilinged premises, the siphon can alternatively be installed so that the air lock is installed somewhere else between the extraction pipes (the parts needed are included in the accessory bag of the siphon package). If this method is used to install the siphon, there must be 47 mm of free space underneath the ventilation unit. When the alternative siphon installation method is used, the ring seal and the locking part must be moved to the pipe connection part that is mounted on the wall.

Installation instructions for the siphon are enclosed with the Vallox Silent Klick siphon package, and can also be found online at http://www.vallox.com.

Important:

The ventilation unit must be installed straight to ensure that condensing water can exit the unit unobstructed. The condensing water pipe must be placed at an angle so that it always points downwards.

Warning:

Water must at all times be kept out of the electrical system.

Wasser in der Elektrik kann zu einem Defekt und zu gefährlichen Verletzungen durch elektrischen Strom führen. Es darf kein Wasser darf in die Elektrik gelangen.

Figure 1. Dimensions of and the space required by the installation of the Vallox Silent Klick siphon (Vallox 90)
Figure 2. Dimensions of and the space required by the installation of the Vallox Silent Klick siphon (Vallox 096/101/110/145 MV)
Figure 3. The space required by the alternative Vallox Silent Klick siphon installation method (elbow) (Vallox 90/096/101/110/145 MV)