Mounting on the wall (Vallox 51K MV)
Note:
Avoid mounting the unit on a hollow, echoing partition wall or on a bedroom wall, or prevent the conduction of sound.
The minimum distance between the top of the unit and the finished ceiling surface is 30 mm. Note that during mounting the unit rises 10 mm higher than the final height.
Vallox 51K MV must be mounted so that the clearance between the bottom of the cooker hood and the cooker top is at least 426 mm in case of an electric stove and 650 mm in case a gas stove. The clearance is 134 mm (i.e. the height of the cooker hood) more between the bottom of the ventilation unit and the cooker top.
Note: A space of at least 330 mm must be reserved in front of the unit
for maintenance purposes
Note: Mount the ventilation unit in a place where the temperature does not fall below +10°C.