Mounting on the ceiling (Vallox 90 MV)

Vallox 90 MV can be equipped with an optional ceiling mount plate. To attach the ceiling mounting plate:

Insulate the outdoor air and exhaust air duct against condensation also between the unit and the ceiling mounting plate.

Mounting the ceiling mounting plate:

  1. Ceiling

  2. Wall

  1. Attach the M8 thread bars to the ceiling and turn the nuts to the bars.

  2. Shorten the lower ends of the thread bars so that they will be at no more than 25mm from the lower surface of the ceiling mounting plate. Thread bars can be shortened only before the ceiling mounting plate is installed.

  3. Lift the ceiling mounting plate in place.

  4. Push a rubber damper (B) and a washer (C) onto each thread bar, and ensure that they touch the bottom of the cups of the plate.

  5. Turn the nuts (A) to make sure that the unit is horizontally level. Lastly, fasten the screws.

Installing the ventilation unit using the ceiling mounting plate:

Warning

The ventilation unit is very heavy. Do not perform this procedure alone.

  1. Remove the front panel (1) of the unit (leave it hanging from the air flow measuring tubes).

  2. Place the connection box cables into the slot in the top part of the side panel (2) and pull the connection box to the side of the unit so that the cables remain in the slot.

  3. Ensure that the condensing water insulation is in place in the duct outlets of the extract air duct and of the duct that comes to the unit from outside.

  4. Lift the unit in its place on the ceiling mounting plate until both locking wings (3) lock on the outer edge of the side plate of the unit.

  5. Visually check the tightness of the duct outlets and the unobstructed passage of measuring tubes and electric cables.

  6. Put the front panel back in place.

Tip

You can detach the unit from the ceiling mounting plate by pulling the spring-loaded moulding to the direction shown by the arrow (more detailed information provided with the ceiling mounting plate).

Attic floor penetration plate

The attic floor penetration plate is optional. When an attic floor penetration plate is used, the tightness of the vapour barrier has to be ensured.

The minimum distance of the attic floor penetration plate from the rear wall is 5mm. The minimum distance of the attic floor penetration plate from the side walls is 15mm.