The ventilation unit is normally installed on the ceiling using the mounting hooks (4 pcs) delivered with the unit. Observe the weight of the unit (45 kg / 58.5 kg) when mounting.
The unit must be installed straight so that the condensing water that collects in the bottom pool drains through the condensing water outlet.
When installed, a space equal to the depth of the unit must be left in front of the unit for servicing purposes.
Table 61. Unit dimensions
Dimension | Vallox TSK Multi 50 MV | Vallox TSK Multi 80 MV |
---|---|---|
A | 431mm | 519mm |
B | 91mm | 91mm |
C | 16mm | 16mm |
D | 548mm | 626mm |
E | 530mm | 600mm |
F | 236mm | 293mm |
G | 935mm | 1060mm |
H | 900mm | 1026mm |
Fold the temperature sensor holder if the supply air duct at the rear of the unit is used. Ensure that the sensor cable is not in contact with the heater.