Sound values

Table 50. Sound power level in the supply air duct

Sound power level in the supply air duct by octave band L dB
Adjustment position21%35%41%50%56%65%72%100%
Air flow dm3/s36.256.367.380.792.9105116128
Air flow m3/h130.32202.68242.28290.52334.44378417.6460.8
Medium frequency of the octave band Hz634150565859646769
1254553565962656871
2505054576163666870
5004853565960636568
10004554576062646667
20003546505558616466
40002641465154586063
80002132384549535659

L dB

5460646769727477

LWA´ dB(A)

4957606366687073


Table 51. Sound power level in the extract air duct

Sound power level in the extract air duct by octave band L dB
Adjustment position21%35%41%50%56%65%72%100%
Air flow dm3/s40.563.873.887.998.9110122136
Air flow m3/h145.8229.68265.68316.44356.04396439.2489.6
Medium frequency of the octave band Hz633554495151565858
1253343464949545659
2502432374040454749
5003743464848525456
10003036394242464850
20002232343838434548
40001620222525313336
80002121212121242628

L dB

4149495557606163

LWA´ dB(A)

3642424850525456


Table 52. Sound pressure level (A)

Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10m2 sound absorption)
Adjustment position21%35%41%50%56%65%72%100%
Air flow dm3/s36/3956/6268/7481/8992/98105/113116/126131/142
Air flow m3/h129.6/140.4201.6/223.2244.8/266.4291.6/320.4331.2/352.8378/406.8417.6/453.6471.6/511.2
LpA´ dB(A)2734374042454750