Sound values

Table 38. Sound power level in the supply air duct

Sound power level in the supply air duct by octave band L dB  
Adjustment position4 %14 %22 %33 %41 %50 %55 %66 %75 %100 %
Air flow dm3/s8.61516.937.745.153.557.367.473.382.3
Air flow m3/h30.965460.84135.72162.36192.6206.28242.64263.88296.28
Medium frequency of the octave band Hz63*56*58*6367707275777980
12552626365676971747678
25044525764706670717274
50040495358616465697174
100032414651555860636768
2000*24344047515557616365
4000*23*253138434850555760
8000*21*21*2330354144515356

L dB

*58*646771747578808284

LWA´ dB(A)

41505460646567707375


Table 39. Sound power level in the extract air duct

Sound power level in the extract air duct by octave band L dB  
Adjustment position4 %14 %22 %33 %41 %50 %55 %66 %75 %100 %
Air flow dm3/s11.324.434.345.655.665.972.68391.599.2
Air flow m3/h40.6887.84123.48164.16200.16237.24261.36298.8329.4357.12
Medium frequency of the octave band Hz6362*53*56*58*616467687071
12552585861646769707374
25035455057606062626263
500*27*344044485153555762
1000*16*232833363942444648
2000*14*17*2329323638414344
4000*16*16*17*21*24*2831343639
8000*20*20*20*20*20*21*22*242629

L dB

62*596164676972737577

LWA´ dB(A)

39434550545557585962


Table 40. Sound pressure level (A)

Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10m2 sound absorption)  
Adjustment position4 %14 %22 %33 %41 %50 %55 %66 %75 %100 %
Air flow dm3/s13/1521/2429/3239/4143/4655/5860/6269/7276/7884/85
Air flow m3/h46.8/5475.6/86.4104.4/115.2140.4/147.6154.8/165.6198/208.8216/223.2248.4/259.2273.6/280.8302.4/306
LpA´ dB(A)*21*263036384243464850