Sound values

Table 32. Sound power level in the supply air duct

Sound power level in the supply air duct by octave band L dB
Adjustment position7%23%37%49%56%67%78%100%
Air flow dm3/s10.625.238.146.653.865.672.976
Air flow m3/h38.1690.72137.16167.76193.68236.16262.44273.6
Medium frequency of the octave band Hz633952616264716968
1253645515658626566
2504151576062656768
5003850545760636566
10003448545759626465
20002443505557616465
40001632424749545658
80002121273438444849

L dB

4557646669737474

LWA´ dB(A)

3952586164676970


Table 33. Sound power level in the extract air duct

Sound power level in the extract air duct by octave band L dB
Adjustment position7%23%37%49%56%67%78%100%
Air flow dm3/s1227.636.744.250.561.070.476.4
Air flow m3/h43.299.36132.12159.12181.8219.6253.44275.04
Medium frequency of the octave band Hz632630404447535457
1252434404649535757
2502233394245495354
5002839444749535556
10002336424548515455
20001324313537414344
40001617212426303333
80002121212121222324

L dB

3343495255596263

LWA´ dB(A)

2839454851545757


Table 34. Sound pressure level (A)

Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10m2 sound absorption)
Adjustment position7%23%37%49%56%67%78%100%
Air flow dm3/s14/1531/3048/4460/5468/6282/7492/8398/89
Air flow m3/h50.4/54111.6/108172.8/158.4216/194.4244.8/223.2295.2/266.4331.2/298.8352.8/320.4
LpA´ dB(A)2329353841444647