Sound values

Table 26. Sound power level in the supply air duct

Sound power level in the supply air duct by octave band L dB
Adjustment position11%28%44%55%62%72%80%100%
Air flow dm3/s9.923.334.843.449.158.765.171.8
Air flow m3/h35.683.9125.3156.2176.8 211.3234.4258.5
Medium frequency of the octave band Hz6352.6*63.2*70.876.475.678.779.380.8
12543.7*56.666.069.672.175.177.178.3
25038.2*44.853.158.160.565.167.369.0
50025.5*33.140.844.647.048.350.051.8
100021.2*33.539.643.645.448.350.051.8
200017.2*19.5*26.3*31.0*33.2*37.0*39.1*41.4*
400018.6*18.9*20.4*24.0*25.9*29.7*32.034.4
800023.7*23.7*23.7*23.8*24.0*24.5*25.0*25.9*

L dB

53.3*64.2*72.177.377.380.481.682.9

LWA´ dB(A)

33.3*43.552.156.858.161.563.464.9


Table 27. Sound power level in the extract air duct

  Sound power level in the extract air duct by octave band L dB
Adjustment position11%28%44%55%62%72%80%100%
Air flow dm3/s (l/s)11.022.035.143.647.959.264.171.4
Air flow m3/h39.679.2126.4157.0172.4213.1230.8257.0
Medium frequency of the octave band Hz6354.7*65.772.777.977.681.782.684.7
12544.2*56.665.869.872.475.778.478.4
25036.7*46.355.459.861.866.568.771.2
50033.342.944.247.950.153.655.557.6
100024.8*34.240.643.945.648.649.951.7
200018.9*25.1*33.838.540.844.746.548.7
400018.6*19.0*24.0*28.9*31.7*36.038.140.6
800023.6*23.6*23.7*24.2*24.9*27.1*28.9*31.0

L dB

55.1*66.273.678.678.882.884.285.8

LWA´ dB(A)

34.9*45.552.957.859.262.664.966.3


Table 28. Sound pressure level (A)

Sound pressure level, in decibels (A) coming through the envelope from the room in which the unit is installed (10m2 sound absorption)
Adjustment position100%80%72%62%55%44%28%11%
Air flow dm3/s71.5/82.865.2/75.058.7/68.848.5/57.943.4/50.935.7/41.422.4/27.911.1/13.8
Air flow m3/h257.4/298.1234.7/270.0211.3/247.7174.6/208.4156.2/183.2128.5/14980.6/100.440/49.7
LpA´ dB(A)43.941.840.138.334.8*30.8*27.0*25.9*