Technical data

Table 18. Technical data

ObjectVallox 90 MV

Product titles

Vallox 90 MV R

Vallox 90 MV L

Type code

3527

Product numbers

3570600 (R model)

3570700 (L model)

HVAC codes

7912066 (R model)

7912067 (L model)

Electrical connection

230V, 50Hz ≈ 5.7A (power plug)

Enclosure protection class

IP 34

Fans

  • Extract air — 0.119kW 0.9A

  • Supply air — 0.119kW 0.9A

Air volumes

  • Supply air — 73dm3/s (259m3/h) 100Pa

  • Extract air — 84dm3/s (302m3/h) 100Pa

Efficiencies

  • Annual efficiency — 62% B

  • Supply air efficiency — 83%

  • Specific Fan Power (SFP) — 1.1 (38dm3/s) B

Heat recovery

Cross-counter flow cell, η = appr. 60%

Heat recovery bypass

Automatic

Post-heating radiator

Electric, 900W

Additional heating radiator

-

Filters

  • Extract air — G4

  • Supply air — G4 and F7

Dimensions without the water seal (width x height x depth)597x689x361mm

Weight

52kg

Ventilation efficiency control

  • MyVallox Control control panel

  • MyVallox Home/Cloud user interface

  • CO2 and %RH control

  • Remote monitoring control (voltage message, Modbus)

Accessories

  • MyVallox carbon dioxide sensor

  • MyVallox humidity sensor

  • MyVallox KNX bus adapter

  • Insulated attic floor penetration plate

  • Ceiling mounting plate

Annual efficiency classification of heat recovery from extract air

B