The ventilation unit is normally installed on the ceiling using the mounting hooks (4 pcs) delivered with the unit. Observe the weight of the unit (45 kg / 58.5 kg) when mounting.
Important
The unit must be installed straight so that the condensing water that collects in the bottom pool drains through the condensing water outlet.
Note
When installed, a space equal to the depth of the unit must be left in front of the unit for servicing purposes.
Table 61. Unit dimensions
Dimension | Vallox TSK Multi 50 MV | Vallox TSK Multi 80 MV |
---|---|---|
A | 431mm | 519mm |
B | 91mm | 91mm |
C | 16mm | 16mm |
D | 548mm | 626mm |
E | 530mm | 600mm |
F | 236mm | 293mm |
G | 935mm | 1060mm |
H | 900mm | 1026mm |
Caution
Fold the temperature sensor holder if the supply air duct at the rear of the unit is used. Ensure that the sensor cable is not in contact with the heater.