Abbreviations used in the table have been explained below:
-
A — Pressure loss in ducts. Total pressure (Pa)
-
B — Volume flow rate (dm3/s)
-
Continuous line (—) — Extract air
-
Broken line (┄) — Supply air
-
PK — An example of pressure loss in the extract air ducts.
-
TK — An example of pressure loss in the supply air ducts.
-
SFP =
SFP rate (Specific Fan Power) recommended value <2.0 (kW m3/s). When a lower total pressure is used, also the SFP of the speed is lowered.
Figure 20. Supply and extract air volumes
Table 25. Fan input power
Fan speeds | Extract air flow (50Pa) dm3/s | Combined input power of the fans W |
---|---|---|
21% | - | 12 |
35% | 10 | 18 |
41% | 22 | 25 |
50% | 33 | 34 |
56% | 46 | 50 |
65% | 60 | 75 |
72% | 75 | 117 |
100% | 92 | 185 |