Technical data

ObjectVallox TSK Multi 50 MV
Product titles

Vallox TSK Multi 50 MV R

Vallox TSK Multi 50 MV L

Type codeA3609
Electrical connection230 V, 50 Hz, 4.5 A power plug
Enclosure protection classIP34
Fans
  • Supply air — 0.043 kW 0.32 A EC
  • Extract air — 0.043 kW 0.32 A EC
Air volumes
  • Supply air — 49 dm3/s, 100 Pa
  • Extract air — 57 dm3/s, 100 Pa
Heat recovery bypassAutomatic
Post-heatingElectrical resistor, 900 W
Pre-heating-
Additional heating-
Filters
  • Supply air — ISO Coarse > 75% + ISO ePM1 ≥ 50 %
  • Extract air — ISO Coarse > 75%
Specific energy consumption (SEC)

In a cold climate — A+

In a temperate climate — A

Operating efficiencies*
  • Annual efficiency — 79%
  • Supply air efficiency — 86%
  • Specific Fan Power (SFP) — 1.3 kW/m3/s (34 dm3/s)
Dimensions (w × h × d)900 x 236 x 547 mm
Weight48 kg
*Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2020.